14-12 Premise isolation

Question: 14-12 Code Section: 7 Date: 17 September 2014 OBC 2012 Reference: 7.6.2.6  Question Submitted:7.6.2.6. Premise Isolation(1) Buildings or facilities where a moderate hazard or severe hazard may be caused by backflow shall be provided with premise isolation of the potable water system by the installation of a backflow preventer selected in accordance with Clauses

14-12 Premise isolation Read More »

08-17 Wall macerating toilet

Question: 08-17 Code Section: 7 Date: 6 July 2008 OBC 2006 Reference: 7.2.2.2.(8), 7.4.3.5, 7.5.7.7 (3),7.4.9.2(4), 7.6.1.5.(1). Question submitted: What type of Backflow protection would you require on the supply line to this macerating toilet Part #48 – Would it have to meet the requirements for an Air Admittance Valve. Interpretation: If the device is

08-17 Wall macerating toilet Read More »