08-17 Wall macerating toilet

Question: 08-17 Code Section: 7 Date: 6 July 2008 OBC 2006 Reference: 7.2.2.2.(8), 7.4.3.5, 7.5.7.7 (3),7.4.9.2(4), 7.6.1.5.(1). Question submitted: What type of Backflow protection would you require on the supply line to this macerating toilet Part #48 – Would it have to meet the requirements for an Air Admittance Valve. Interpretation: If the device is …

08-17 Wall macerating toilet Read More »

14-10 PRV installation

Question: 14-10 Code Section: 7 Date: 10 September 2014 OBC 2012 Reference: Question Submitted: We recently had a backflow inspection for a 2” DCVA for an apartments premise protection. The pressure coming into the building exceeds 100psi and because the expansion tank is only rated for a maximum pressure of 80psi we had to install …