Question: 09-14 | Code Section: 7 | Date: 14 September 2009 | OBC 2006 Reference: 7.5.7.1.(1) |
Question: A sewage tank with a 3″ vent … would a 1 1/2″ waste from a laundry tub fixture be allowed to discharge into the vent.
Interpretation: No, an ejector vent cannot be wet vented, nor can its vent serve as a wet vent. 7.5.2.1.(1) states that only a fixture served by a soil or waste pipe can serve as a wet vent.
Interpretation: Approved at AMES 2009