Question: 05-22 | Code Section: 7 | Date: | OBC 2006 Reference: |
Question: On the attached picture (condensate for HRV and Furnace): Do I have to vent through the roof?
Interpretation: (On. Reg. 403/97) Section 7.4.2.3(3) indicates that the vent must go through the roof when fixtures are on 3 or more stories. Traps are required to prevent air flow from one unit to another on adjacent levels.