Question: 13-06 Code Section: 7 Date: 15 September 2009

OBC 2006 Reference: 7.7.1.1.(1)

Question: Is it permitted or acceptable to interconnect a grey water system with a potable water system as long as the potable water system is protected by means of an RP?

Interpretation: Yes, a potable water system may supply a grey water system through an RP.

Approved at AMES 2009 